Biogas chiller GC-1500-35-10

Biogas chiller GC-1500-35-10

Biogas drying at 1 500 Nm³/h · 35 → 10 °C

Application

GC-1500-35-10 is a refrigerated biogas dryer for gas treatment upstream of gas-consuming equipment. The nominal flow is 1 500 Nm³/h; gas enters at 35 °C and leaves the cooler at 10 °C. Cooling removes part of the water vapour as condensate and reduces liquid moisture entering subsequent gas-treatment stages.

Operating principle

Biogas passes through the gas heat exchanger and transfers heat to the refrigeration circuit. Cooling to 10 °C causes water vapour to condense. A gas-liquid separator with a mesh demister captures droplets, and an automatic drain removes the collected liquid. The separated gas remains saturated with water vapour at its outlet temperature; further cooling in the pipework can cause condensation again.

Refrigeration circuit

The selected duty provides a cooling capacity of 107 kW. The refrigeration module comprises a compressor circuit and an air-cooled condenser. Heat is discharged to the ambient air. Refrigeration control maintains the specified gas temperature as the load changes. Unrestricted airflow through the condenser is required for heat rejection.

Materials and configuration

The gas-contact surfaces of the heat exchanger and separation assembly are made of AISI 316L stainless steel. The casing and supporting structure are steel with a protective coating. Cold surfaces and condensate lines are insulated. Drain-line heating is provided for operation below freezing. The standard configuration is intended for installation outside hazardous areas.

Control

The automation system provides local start and stop, temperature monitoring, operating indication and fault indication. The touchscreen displays parameters and operating history. Functions include high- and low-pressure protection for the refrigeration circuit, motor overload protection, remote start and stop, fault signalling and data exchange via RS485 / Modbus RTU.

Connections and operation

The unit requires a 400 V, three-phase, 50 Hz supply. The nominal flow of 1 500 Nm³/h refers to normal conditions of 0 °C and 1.013 bar. Coarse mechanical impurities and liquid slugs must be prevented from entering the dryer. Access to the heat exchanger, condensate drain and electrical cabinet must be provided for maintenance.

Options

Gas reheating after drying can reduce relative humidity before downstream equipment. A reheater, activated carbon filter, gas blower, external pipework and installation work are not included in the stated chiller price. Versions for a different electrical supply or special operating conditions are ordered separately.

Per unit, EUR, excluding VAT, EXW. Packaging, freight, installation and commissioning are charged separately. Gas reheating is not included.

Technical specifications
Scope of supply

Model

GC-1500-35-10

Nominal biogas flow

1 500 Nm³/h

Normal flow conditions

0 °C; 1.013 bar

Gas inlet temperature

35 °C

Gas outlet temperature

10 °C

Relative humidity at inlet

100 %

Relative humidity at outlet before reheating

100 %

Cooling capacity

107 kW

Electrical power

37 kW

Condensate removal at nominal duty

56.1 kg/h

Power supply

400 V / 3 phases / 50 Hz

Condenser cooling

Air-cooled

Gas-contact materials

AISI 316L stainless steel

Condensate drainage

Automatic, with drain heating

Control

Controller and touchscreen

Remote control

Start / stop, fault signal; RS485 / Modbus RTU

Ambient temperature

−20…+42 °C

Installation location

Outside hazardous areas

Technical specifications

Model

GC-1500-35-10

Nominal biogas flow

1 500 Nm³/h

Normal flow conditions

0 °C; 1.013 bar

Gas inlet temperature

35 °C

Gas outlet temperature

10 °C

Relative humidity at inlet

100 %

Relative humidity at outlet before reheating

100 %

Cooling capacity

107 kW

Electrical power

37 kW

Condensate removal at nominal duty

56.1 kg/h

Power supply

400 V / 3 phases / 50 Hz

Condenser cooling

Air-cooled

Gas-contact materials

AISI 316L stainless steel

Condensate drainage

Automatic, with drain heating

Control

Controller and touchscreen

Remote control

Start / stop, fault signal; RS485 / Modbus RTU

Ambient temperature

−20…+42 °C

Installation location

Outside hazardous areas

Scope of supply

Refrigeration compressor module

air-cooled condenser with fans

AISI 316L gas heat exchanger

gas-liquid separator with mesh demister

automatic condensate drain and manual drain

cold-surface insulation

drain-line heating

casing and supporting structure

control cabinet with controller and touchscreen

sensors, protective controls and standard internal connections

operating documentation.