Open gas flare FAI 15 DN15 auto

To reduce the operating efforts the FAI series offers an automatic update. These improved versions add to the manual version an automatic gas valve, a UV flame detector plus a control system based on a automatic burner control fully complying with EU normatives.

For operating the automatic versions just change the selector to start, the flare will open the valve and ignite the gas by itself. In case that the flame is lost, the UV detector will close the valve to avoid malfunctions. To stop the combustion, change the selector to stop.

Advanced options such as transformer for battery usage, anti-freeze configuration, pressure control or blower, are available to make the use of the FAI the most comfortable possible.

All Zorg Biogas FAI biogas flares are entirely made of stainless steel 1.4571 (316Ti), and fitted with high quality components, plus a robust design that ensures a constant long working life with a low maintenance.
 
Main characteristics:
- Low-temperature combustion with open flame at a temperature of 850-900 ° C.
- Max Biogas flow 15 nm³ / h at 2,5 mbar
- Max Biogas flow 36 nm³ / h at 20 mbar
- Thermal power: max 97,5 kW 
- Methane content (CH4): 45-99 Vol.%
- Income Pressure (P) de: 55 mbar (with flow 40 m3 per hour)
- Flange connection DN 15
 
Dimensions:
Height 4000 mm
Diameter 356 mm
Weight 160 kg
 
Material:
- Type of combustion: Open combustion
- Combustion chamber: Stainless steel 1.4404/1.4571 (AISI 316L / AISI 316 Ti)
- Gas pipe: Stainless steel 1.4404/1.4571 (AISI 316L / AISI 316 Ti)
- Frame/Substructure: Stainless steel 1.4301 (AISI 304)
- Flame Arrester: ATEX certified
- Supply voltage 230V/50Hz
- The documentation will be provided in German or English language incl. CE conformity certificate (1 x in paper, 1 x digital)
 
Scope of Supply:
- Ignition transformer (7.5kV)
- Ignition by electrodes
- Condensate discharge by manual ball valve
- Manual gas flap with DVGW certificate
- Control unit with Kromschröder IFD 258 automatic gas burner control, according to EN 746-2, hard-wired.
- PLC Siemens Logo! 8
- Communication and control: Hard-wired or via Ethernet
- IP / Modbus TCP
- Control cabinet IP66;supply voltage  230V/50Hz
(others on request)
- Low pressure switch
- Flame monitoring with UV sensor
- Automatic solenoid/motor valve
 
OPTIONS:
- Blower 1,5-2,2 kW. DN125 PN16. Motor 3G Zone 2. 100-700 m3/h. 25-40 mbar. Aluminium.
- Blower integration into flare control board (up to 4 kW)
- Flare functioning depending on pressure in line (pressure switches)
- High grade steel control board
Technical Details
Features
Optional Features

Gas connection DN:

15 mm

Operating pressure:

2 – 40 mbar

Flow rate:

15-30 Nm³/h

Technical Details

Gas connection DN:

15 mm

Operating pressure:

2 – 40 mbar

Flow rate:

15-30 Nm³/h

Features

Automatic operation

Combinable with blower

Optional Features

Advanced options such as transformer for battery usage, anti-freeze configuration, pressure control or blower, are available to make the use of the FAI gas flare the most convenient possible.

We can also offer special operating flows and pressures on request.

Other goods

Enclosed biogas flare FAII 50v
Open gas flare FAI 200 DN65 manual
Open flare FAI50 DN40 manual