Semi-enclosed gas flare FAII 2200 DN200

Application

FAII 2200 is a semi-enclosed gas flare for controlled disposal of surplus gas during maintenance or shutdown of a CHP unit or other gas-consuming equipment. Automatic flare startup allows gas that cannot currently be used for energy production to be burned. The model selection range is 1,800–2,200 Nm³/h; the operating point is agreed for the gas composition and inlet pressure.

Flow, pressure and dimensions

Operating point: 2,200 Nm³/h at an inlet gauge pressure of 25 mbar. Overall height: 7,600 mm; chamber diameter: 2,200 mm. Dimensions refer to the standard semi-enclosed configuration.

Suitable gases

The flare is selected for biogas, biomethane, landfill gas and other methane-based gases. For hydrogen blends, the permitted H₂ fraction is agreed for the selected burners, valves and protection. Stated flows and pressures refer to the reference design gas; changes in composition require confirmation of the operating characteristic.

Semi-enclosed design

The burners sit inside a vertical metal shroud that shields the combustion zone from precipitation and external influences. Under optimum conditions, most of the flame remains inside, but it may extend above the upper rim. This must be considered when locating the flare. The model suits sites where semi-enclosed combustion is permitted; a different design is selected if a fully concealed flame is required.

Burners and materials

Injector burners mix gas with primary air before combustion. Secondary air enters naturally from below; the air supply is adjusted during commissioning. This supports stable combustion within the agreed operating range. Replaceable burner heads simplify maintenance. Gas-contact parts are made of corrosion-resistant stainless steel, and the support structure is AISI 304 stainless steel.

Automatic operation

A start command initiates the valve-opening and electric ignition sequence. A UV sensor continuously monitors the flame. If ignition fails or the flame goes out, the controls stop the gas supply and follow the specified restart sequence or signal a fault. Low-pressure protection prevents operation with insufficient gas pressure. Automatic shut-off valves close on loss of electrical power.

Gas connection

One external DN200 gas inlet. Downstream of the common inlet, gas is distributed to 2 internal DN125 lines. These belong to the flare gas train and are not separate external connections. DN is the nominal connection size, not the pipe outside diameter. Inlet position, mating flange and supply-pipe route are agreed using the installation drawing. A condensate drain with a manual ball valve is provided. The supply pipeline is designed for the flow, available pressure and condensate removal.

Control

The IP66 control panel contains a burner control unit and Profinet/Profibus communication modules for connection to the external biogas plant PLC. It provides local operation, status indication, and remote start and control from the plant PLC. The external PLC is not included in the supply. Power supply: 230 V, 50 Hz. Automatic starting based on gas-line pressure is available as an additional function.

Optional configurations

Options include a pilot burner, valve heating and insulation, temperature monitoring, a stainless-steel control panel and a version for elevated H₂S levels. Chamber heat resistance and operating duty are agreed separately for prolonged or continuous use. Pneumatic valves require dry compressed air; a compressor is provided where necessary. Cold-climate equipment is selected for the site's minimum temperature.

Installation and selection

The flare is installed vertically on a prepared foundation and secured as shown in the installation drawing. Earthing, access to valves and the control panel, and adequate clearance around the combustion zone are required. Selection considers minimum and maximum flow, methane and hydrogen sulphide content, gas pressure and operating periods. Foundation, supply connections, delivery and installation are agreed separately from the equipment package.

Technical specifications
Advantages
Complete set

Model

FAII 2200

Design

Semi-enclosed flare

Suitable gases

Biogas, biomethane, landfill and other methane-based gases; permitted H₂ content to be agreed

Model selection flow range

1,800–2,200 Nm³/h

Number of external gas inlets

1

Nominal inlet size

DN200

Internal gas lines

2 × DN125

Flow at the operating point

2,200 Nm³/h

Inlet gauge pressure at the operating point

25 mbar

Overall height

7,600 mm

Combustion chamber diameter

2,200 mm

Burner type

Premixing injector burners

Ignition

Automatic electric ignition

Flame monitoring

UV sensor

Control panel

IP66, Profinet/Profibus communication modules

Power supply

230 V, 50 Hz

Support structure material

AISI 304 stainless steel

Gas-contact material

Corrosion-resistant stainless steel

Remote start and control

From the external plant PLC; PLC not included in the supply

Technical specifications

Model

FAII 2200

Design

Semi-enclosed flare

Suitable gases

Biogas, biomethane, landfill and other methane-based gases; permitted H₂ content to be agreed

Model selection flow range

1,800–2,200 Nm³/h

Number of external gas inlets

1

Nominal inlet size

DN200

Internal gas lines

2 × DN125

Flow at the operating point

2,200 Nm³/h

Inlet gauge pressure at the operating point

25 mbar

Overall height

7,600 mm

Combustion chamber diameter

2,200 mm

Burner type

Premixing injector burners

Ignition

Automatic electric ignition

Flame monitoring

UV sensor

Control panel

IP66, Profinet/Profibus communication modules

Power supply

230 V, 50 Hz

Support structure material

AISI 304 stainless steel

Gas-contact material

Corrosion-resistant stainless steel

Remote start and control

From the external plant PLC; PLC not included in the supply

Advantages

Automatic flare startup and UV flame monitoring

Remote start and control from the external plant PLC

Complete set

Flare stack with protective shroud and support structure

injector burners and gas train

manual isolation valve

automatic gas shut-off valves

flame arrester

condensate drain

electric ignition system

UV flame monitoring

low gas pressure protection

IP66 control panel with Profinet/Profibus communication modules

standard fasteners and operating documentation. The external plant PLC is not included. The gas train includes one common DN200 inlet and 2 internal DN125 lines.

Other goods

Enclosed biogas flare FAII 800v DN125
Enclosed biogas flare FAII 500v DN100
Enclosed biogas flare FAII 400v DN100
Enclosed biogas flare FAII 300v DN80
Fully-enclosed flare FAII 200v DN65 with automatic control
Fully-enclosed flare FAII 100v DN50 with automatic control